- Head mount
- Programmable for various input signals and measuring range
- Configurable without Power Connected
- 3750 Vrms isolation between input and output
- INPUTS: Resistance thermometer (PT100)
Thermocouple (J,K,T,,B,R,S,N,C)
Fault signal on sensor break presettable
Input |
Thermocouple (T/C): Industry standard thermocouple types J,K,T,E,B,R,S,N,C (ITS-90) |
PT100: Excitation 180uA, 2 or 3 wire connection (ITS-90α=0.00385) |
|
Voltage: -60mVdc to 60mVdc or-10Vdc to 10Vdc. |
|
Current: 0-24mAdc |
|
Accuracy |
Refer to Table 1 input Signal |
A/D Resolution |
16 bits |
Input Sampling Rate |
<200ms |
Power supply |
DC 10 to 36V |
Max. Load |
(V-10) / 0.02 (Ω) |
Output Resolution |
0.6 uA (15 bits) |
Output Response time |
<200ms |
Common Mode Rejection Ratio(CMRR) |
>80dB |
Electromagnetic compatibility |
En 50081-2, En 50082-2 |
Galvanic isolation |
3.75 KV. Between input and output |
Operating Temperature |
-10 to 50 C |
Humidity |
0 to 90% RH |