2-wire RTD type Temperature transmitter for Head-mounting

  • Linearised temperature measurement with PT100Ω sensor.
  • To avoid temperature signal attenuation during long-distance transmission, it converts PT100Ω into standard analog current output 4-20mA DC (2-wire)
  • In this way, a stable and accurate figure can be collected and shown on the display of terminal instrument. The instrument includes PLC, digital display, industrial computer, etc.
 Add to Inquiry

INPUT

Input

PT 100Ω (3-wire)

Cable resistance

≦50Ω (3 wires with the same resistance)

PT100Ω sensor current

< 0.8mA

ZERO adjustment range

± 10 %

SPAN adjustment range

± 10 %

OUTPUT

Output

4-20mA; 2-wire

Accuracy

± 1 % of F.S.

Load resistance

≦ (supply voltage-8V) / 0.02AΩ

Load resistance stability

± 0.05% / 100Ω

Power supply stability

± 0.25% / V

Temperature drift

<±0.015% F.S. / ℃

Calibration temperature

20 ~ 28 ℃

Response time

< 250 ms

PROTECTION

PT100Ω signal disconnection protection & output

>23mA

PT100Ω signal short circuit, protection & output

<3mA

Output polarity protection

Yes

ELECTRICAL SPECIFICATION

Power supply

10 ~ 30 VDC

Working temperature

-20 ~ 60 ℃

Working humidity

0~95% RH (non-cond.)

Protection degree

Housing:IP30 ; Terminal:IP10

Housing

ABS (UL94V-0)

Weight

40g